Energy Meter
Pramp Automation and Calibration
Category: Indicators Controllers
Product: Energy Meter
Dual Source Energy Meter (Single Phase and Three Phase)
Description:
Display |
7 segment LED DISPLAY |
Auxiliary Supply |
90 – 270VAC/DC |
Burden On Supply |
<3 VA |
Digit |
1 row of 8 Digits(for energy), 1 rows of 4 digits (For parameter Display) |
Input Volts |
0-500VAC (L-L), 3Ø-4 Wire / 1Ø-2 Wire |
Input Ampere |
0.015A-6.00 Ampere AC / 60 Ampere direct optional |
Resolution |
Energy 0.1 kWh, PF 0.001, Hz 0.01 & Auto ranging for Voltage, Current & Power |
CT Primary |
Programmable for up to 10000A |
CT Secondary |
1A / 5A Programmable |
PT Ratio |
Up to 132 Kv |
Communication |
RS485 MODBUS |
Update Time / Scroll |
1 Sec / Auto / Manual |
Temp./ Humidity |
Operating: -10°C to 55°C, Storage: -20°C to 75°C < 95% RH |
Duca LCD
Description
- 96×96 panel mounting analyzer
- Large white-backlit LCD
- User-selectable backlight intensity level
- 4 measurements simultaneously displayed
- 146 displayed measurements
- Max-demand measurement
- Measurement accuracy: class 1
- Accuracy of primary measurements: 0,5%
- High accuracy thanks to “oversampling” techniques and automatic calibration process
- Automatic detection of CTs current flow for easy installation
- Autotest for quickly insertion check
- User-friendly interface thanks to 5 buttons for quick menu-scroll
- Easy setting of CT/VT ratio
- ThdF measurement (all phases) for distortion on voltage and current with % and absolute values
- Cogeneration mode selectable (2 or 4 quadrants) with separate counters and full instant balance indication
- Indication of partial energy for monitoring industrial processing cycles
- Energy conversion to money (€) and CO2 production (also in cogeneration mode)
- 2 pulses outputs selectable as energy pulses or alarm outputs on 29 measures
- User selectable operation mode based on insertion-type (single-phase, three-phase, balanced three-phase, generic)
- User-Password protection
- User-selectable interface-language
- User selectable default displayed page
- Free-running timer for instrument “life-time” and count-down timer for “process working-time” (programmable counting threshold)
- Wide range power supply 24 ÷ 240VAC/DC (48 ÷ 240VAC/DC for “PROFI”, “ETH” and “IO” models)
- Low internal depth (58mm inside the panel) even for optional models
- Standard Model with integrated CTs; “BASE” Model with shunt input stage
- “485” Model with RS-485 interface: ASCII-Ducati and Modbus-RTU protocols user selectable
- “RELE” Model with booster-relay (250V-16A) for 2 additional alarm outputs and loads control
- “IO” Model with 2 insulated analog-outputs (0-20/4-20mA) and 3 insulated pulse-inputs for energy reading from GME counters
- “PROFI” Model with optically-insulated Profibus interface with DP-slave option according to IEC-61158
- “ETH” model with built-in Webserver and Modbus-TCP communication protocol, Ethernet RJ45 insulated interface connector with auto MDI / MDX crossover functionality